|
Electricians' toolbox
Electrical Definitions
Accessible - (As applied to wiring methods)
Capable of being removed or exposed without damaging the building
structure or finish, or not permanently closed in by the structure
or finish of the building.
Accessible - (as applied to equipment) Admitting
close approach: not guarded by locked doors, elevation, or
other effective means. (see Accessible, Readily)
Accessible, Readily - (Readily Accessible)
Capable of being reached quickly for operation, renewal, or
inspections, without requiring those to whom ready access
is requisite to climb over or remove obstacles or to resort
to portable ladders,chairs,etc.
Ambient Temperature - The temperature of
the air, water, or surrounding earth. Conductor ampacity is
corrected for changes in ambient temperature including temperatures
below 86°F. The cooling effect can increase the current
carrying capacity of the conductor. (Review Section 310-10
of the Electrical Code for more understanding)
Ammeter - An electric meter used to measure
current, calibrated in amperes.
Ampacity - The current-carrying capacity
of conductors or equipment, expressed in amperes.
Ampere - The basic SI unit measuring the
quantity of electricity.
Bonding Jumper - A bare or insulated conductor
used to ensure the required electrical conductivity between
metal parts required to be electrically connected. Frequently
used from a bonding bushing to the service equipment enclosure
to provide a path around concentric knockouts in an enclosure
wall: also used to bond one raceway to another.
Continuity - The state of being whole, unbroken.
Continuos Load - A load where the maximum
current is expected to continue for three hours or more. Rating
of the branch circuit protection device shall not be less
tan 125% of the continuos load.
Demand Factor - For an electrical system
or feeder circuit, this is a ratio of the amount of connected
load (in kva or amperes) that will be operating at the same
time to the total amount of connected load on the circuit.
An 80% demand factor, for instance, indicates that only 80%
of the connected load on a circuit will ever be operating
at the same time. Conductor capacity can be based on that
amount of load.
Dustproof - Constructed or protected so
that dust will not interfere with its successful operation.
Dusttight - Constructed so that dust will
not enter the enclosing case under specified test conditions.
Duty, continuos - A service requirement
that demands operation at a substantially constant load for
an indefinitely long time.
Duty, intermittent - A service requirement
that demands operation for alternate intervals of load and
no load, load and rest, or load, no load, and rest.
Duty, periodic - A type of intermittent
duty in which the load conditions regularly reoccur.
Duty, short time - A requirement of service
that demands operations at a substantially constant load for
a short and definitely specified time.
Duty, varying - A requirement of of service
that demands operation at loads, and for intervals of time,
both of which may be subject to wide variation.
Explosionproof - Designed and constructed
to withstand and internal explosion without creating an external
explosion or fire.
Feeder - A circuit, such as conductors in
conduit or a busway run, which carries a large block of power
from the service equipment to a sub-feeder panel or a branch
circuit panel or to some point at which the block power is
broken into smaller circuits.
Ground - A large conducting body (as the
earth) used as a common return for an electric circuit and
as an arbitrary zero of potential.
Grounded, effectively - Intentionally connected
to earth through a ground connection or connections of sufficiently
low impedance and having sufficient current-carrying capacity
to prevent the buildup of voltages that may result in undue
hazards to connect equipment or to persons.
Grounded Conductor - A system or circuit
conductor that is intentionally grounded, usually gray or
white in color.
Grounding Conductor - A conductor used to
connect metal equipment enclosures and/or the system grounded
conductor to a grounding electrode, such as the ground wire
run to the water pipe at a service; also may be a bare or
insulated conductor used to ground motor frames, panel boxes,
and other metal equipment enclosures used throughout electrical
systems. In most conduit systems, the conduit is used as the
ground conductor.
Grounding Equipment Conductor - The conductor
used to connect the noncurrent-carrying metal parts of equipment,
raceways, and other enclosures to the system grounded conductor,
the grounding electrode conductor, or both, of the circuit
at the service equipment or at the source of a separately
derived system.
Grounding Electrode - The conductor used
to connect the grounding electrode to the equipment grounding
conductor, to the grounded conductor, or to both, of the circuit
at the service equipment or at the source of a separately
derived system.
Ground Fault Circuit Interrupter - A device
intended for the protection of personal that functions to
de-energize a circuit or portion thereof within an established
period of time when a current to ground exceeds some predetermined
value that is less than required to operate the overcurrent
protection device of the supply circuit.
Ground Fault Protection of Equipment - A
system intended to provide protection of equipment from damaging
line to ground fault currents by operating to cause a disconnecting
means to open all ungrounded conductors of the faulted circuit.
This protection is provided at current levels less than those
required to protect conductors from damage through the operations
of a supply circuit overcurrent device.
In Sight From - (within sight from, within
sight) Where this Code specifies that one equipment shall
be "in sight from", "within sight from"
or m"within sight", etc. of another equipment, the
specified equipment is to be visible and not more that 50´
distant from the other
Interrupter Rating - The highest current
at rated voltage that a device is intended to interrupt under
standard test conditions.
Labeled - Items to which a label, trademark,
or other identifying mark of nationally recognized testing
labs has been attached to indentify the items as having been
tested and meeting appropriate standards.
Listed - Equipment or materials included
in a list published by an organization acceptable to the authority
having jurisdiction and concerned with product evaluation,
that maintains periodic inspection of production of listed
equipment or materials, and whose listing states either that
the equipment or material meets appropriate designated standards
or has been tested and found suitable for use in specified
manner.
Location, damp - A location subject to moderate
amount of moisture such as some basements, barns, cold storage,
warehouse and the like.
Location, dry - A location not normally
subject to dampness or wetness: a location classified as dry
may be temporarily subject to dampness or wetness, as in case
of a building under construction.
Location, wet - A location subject to saturation
with water or other liquids.
Megger - A test instrument fpr measuring
the insulation resistance of conductors and other electrical
equipment; specifically, a megaohm (million ohms) meter; this
is a regiestered trade mark of the James Biddle Co.
Megaohm - A unit of electrical resistamce
equal to one million ohms.
Megaohmmeter - An instrument for measuring
extremely high resistance.
Noninductive Circuit - A circuit in which
the magnetic effect of the current flowing has been reduced
by one several methods to a minimum or to zero.
Nonlinear Load - A load where the wave shape
of the steady state current does not follow the wave shape
of the applied voltage.
Ohm - The derived SI unit for electrical
resistance or impedance; one ohm equals one volt per am-pere.
Ohmmeter - an instrument for measuring resistance
in ohms. Take a look at this diagram to see how an ohmeter
is used to check a small control transformer. The ohmmeter's
pointer deflection is controlled by the amount of battery
current passing through the moving coil. Before measuring
the resistance of an unknown resistor or electrical circuit,
the ohmmeter must first be calibrated. If the value of resistance
to be measured can be estimated within reasonable limits,
a range selected that will give approximately half-scale deflection
when the resistance is inserted between the probes. If the
resistance is unknown, the selector switch is set on the highest
scale. Whatever range is selected, the meter must be calibrated
to read zero before the unknown resistance is measured.
Overcurrent - Any current in excess of the
rated current of equipment or the ampacity of a conductor.
It may result from overload, short circuit or ground fault.
Overload - Load greater than the load for
which the system or mechanism was intended. A fault, such
as a short circuit or ground fault, is not an overload.
Panelboard - A single panel or group of
panel units designed for assembly in the form of a single
panel: includes buses and may come with or without switches
and/or automatic overcurrent protective devices for the control
of light, heat, or power circuits of individual as well as
aggregate capacity. It is designed to be placed in a cabinet
or cutout box that is in or against a wall or partition and
is accessible only from the front.
Plenum - Chamber or space forming a part
of an air conditioning system
Rainproof - So constructed, projected, or
treated as to prevent rain from interfering with the successful
operation of the apparatus under specified test conditions.
Raintight - So constructed or protected
that exposure to a beating rain will not result in the entrance
of water.
Separately Derived System - A premises wiring
system whose power is derived from a battery, a solar photovoltaic
system, or from a generator, transformer, or converter windings,
and that has no direct electrical connection, including solidly
connected grounded circuit conductor, to supply conductors
originating in another system.
Service Drop - Run of cables from the power
company's aerial power lines to the point of connection to
a customer's premises.
Service Conductors - The supply conductors
that extend from the street main or transformers to the service
equipment of the premises being supplied
Service Entrance Conductors - (Overhead)
The service conductors between the terminals of the service
equipment and a point usually outside the building, clear
of building walls, where joined by tap or splice to the service
drop.
Service Entrance Conductors - (Underground)
The service conductors between the terminals of the service
equipment and the point of connection to the service lateral.
Service Equipment - The necessary equipment,
usually consisting of a circuit breaker or switch and fuses
and their accessories, located near the point entrance of
supply conductors to a building and intended to constitute
the main control and cutoff means for the supply to the building.
Service Lateral - The underground service
conductors between the street main, including any risers at
a pole or other structure or from transformers, and the first
point of connection to the service-entrance conductors in
a terminal box, meter, or other enclosure with adequate space,
inside or outside the building wall. Where there is no terminal
box, meter, or other enclosure with adequate space, the point
of connection is the entrance point of the service conductors
into the building.
Service Point - The point of connection
between the facilities of the serving utility and the premises
wiring.
Switchboard - A large single panel, frame,
or assembly of panels having switches, overcurrent, and other
protective devices, buses, and usually instruments mounted
on the face or back or both. Switchboards are generally accessible
from the rear and from the front and are not intended to be
installed in cabinets.
Switch, general use - A switch intended
for use in general distribution and branch circuits. It is
rated in amperes and is capable of interrupting its rated
voltage.
Switch, general-use snap - A type of general-use
switch so constructed that it can be installed in flush device
boxes or on outlet covers, or otherwise used in conjunction
with wiring systems recognized by the National Electric Code.
Switch, isolating - A switch intended for
isolating an electrical circuit from the source of power.
It has no interrupting rating and is intended to be operated
only after the circuit has been opened by some other means.
Switch, knife - A switch in which the circuit
is closed by a moving blade engaging contact clips.
Switch, motor-circuit - A switch, rated
in horsepower, capable of interrupting the maximum operating
overload current of a motor of the same horsepower rating
as the switch at the rated voltage.
Switch, transfer - A transfer switch is
an automatic or nonautomatic device for transferring one or
more load conductor connections from one power source to another.
Switch-Leg - That part of a circuit run
from a lighting outlet box where a luminaire or lampholder
is installed down to an outlet box that contains the wall
switch that turns the light or other load on or off: it is
a control leg of the branch circuit.
Voltage Drop - The loss of voltage between
the input to a device and the output from a device due to
the internal impedance or resistance of the device. In all
electrical systems, the conductors should be sized so that
the voltage drop never exceeds 3% for power, heating, and
lighting loads or combinations of these. Furthermore, the
maximum total voltage drop for conductors for feeders and
branch circuits combined should never exceed 5%.
Watertight - So constructed that water/moisture
will not enter the enclosure under specified test conditions.
Weatherproof - So constructed or protected
that exposure to the weather will not interfere with successful
operation.
Back to Electrician's Toolbox |